ATEX Certified Heated Diode Refrigerant Leak Detector
Product
- Sensor Type: Heated diode
- Sensor Life: 300 hours typical
- Sensitivity Levels: High, medium, low (selectable)
- Maximum Sensitivity: 1g/a, stationary; 3g/a, in motion
- Detection Feedback: Flashing LED, LCD bar graph and digits, audible beep, Job Link® app
- Refrigerants: HC, HFC, HCFC, CFC, HFO, H2/N2 (Tracer Gas: 5% Hydrogen, 95% Nitrogen), and blends.
- For Use With: A3 (R-290, R-600A, R-600, R-50, R-1270), A2L (Including R32, R1234yf, R1234ze), and A1 refrigerants.
- Not For Use With: R-702, R-717, R-744
- ATEX Rating: II 3 G Ex ic IIA T2 Gc
- Operating Environment: -20°C to 50°C (-4°F to 122°F); < 95% RH (non-condensing)
- Battery Type: 4x Replaceable AA Lithium Iron Disulfide (to maintain ATEX compliance, use 4 x Energizer (L91 AA batteries.)
- Battery Capacity: 1.5 VDC (nominal) 3500 mAh
- Battery Life: 60 hours typical
- Auto Power Off: 10 minutes without detection or button press
- Radio Frequency: 2.4 GHz
- Wireless Range: Up to 305 meters (1000 feet) line of sight
- Storage Temperature: -20°C to 60°C (-4°F to 140°F); < 95% RH (non-condensing)
- Weight: 442g (15.6 oz) with Batteries Installed
- Water Resistance: IP54 Main Body